Created with Pixso. Home Created with Pixso. Products Created with Pixso.
Stationary Meter Test System
Created with Pixso.

Stationary Three Phase Meter Test System

Stationary Three Phase Meter Test System

Brand Name: GENY
Model Number: YC-1893R
MOQ: 1 Sets
Price: Negotiable
Payment Terms: T/T,L/C,D/P,T/T
Supply Ability: 10 pcs/ 3 months
Detail Information
Place of Origin:
CHINA
Certification:
ISO, CE
Model No.:
YC1893R
Accuracy Class:
0.01%
Meter Position:
1~ 6
Frequency Range:
40Hz ~ 70Hz
Conformity:
CE Conform
Reference Class:
0.01% / 0.005%
Waveform Distortion:
Less Than 0.05%
IP Class:
IP30
Packaging Details:
Plywood cases
Supply Ability:
10 pcs/ 3 months
Highlight:

three phase meter test system

,

stationary meter test bench

,

stationary meter test system

Product Description

High Accuracy Stationary Three Phase Meter Test System for Testing of Electronic Electric Energy Meters

YC1893R series is developed by our company with international advanced level of high-grade equipment. The overall accuracy levels up to 0.01 grades. It Is designed for institute of metrology, laboratory, EPRI and EEM equipment plants. It is mainly used to establish primary standards or the standards meter for the working standard .

This is a Stationary Three-phase Energy Meter Test System described here can simultaneously test 1…3, three-phase or single-phase electric energy meters, in which are 2-wire, 3-wire and 4-wire meters for active and reactive energy with accuracy of 0.1%, 0.2%, 0.5%, 1.0%, 2.0%.

The Meter Test System has following features and functions

  • Supporting parallel communication port to test smart meters through RS232 / Ethernet
  • Calibrating terminals on the rack for test bench verification
  • 1-phase energy meter for testing
  • 3-phase energy meter for testing
  • Accuracy Testing of reference standard meter
  • Pre-warming
  • Accuracy test as per IEC
  • Creeping test
  • Starting current test
  • Repeatability of error test
  • Dial test
  • Influence quantity test related to accuracy tests (Voltage, Frequency, reverse phase sequence, voltage unbalance)
  • Influence of harmonic component in voltage and current circuit as per IEC
  • Tamper and Fraud Monitoring
  • Sub Harmonics as per IEC standards (IEC 62052-11 / 62053-21/22/23)
  • Odd Harmonics as per IEC standards


Main Technical Data


  • Overall accuracy: 0.01%
  • Meter position: 1~3
  • Voltage output: 3x 480 VAC
  • Power voltage: 3x 70 VA or customized
  • Current output: 3x 1mA - 120A
  • Power current: 3x 300VA or customized
  • Stability: 30 ppm/h
  • Harmonic: 2nd - 41st


Technical Parameters


Voltage 240/415 V AC supply (+5% & -10%) or customized
Frequency 50/60Hz ±2Hz
Power capacity > 3 × 6kVA
Ambient temperature -10°C … +40°C
Relative humidity 35% … 95%
System Grounding Neutral solidly grounded
Surge protection level ≥ 10 kV/120 Joules (10/1000µs)


Voltage
Test voltage output (Phase-Neutral) 3× (24V - 500V) or customized
Power of the voltage output 3×100VA
Resolution Better than 0.01% of full scale value of range
Setting accuracy Better than 0.05% at the final range value
Stability Better than 0.003%/h (integration time 150 s)
Load regulation from 0-max. load < 0.01%
Distortion factor < 0.3% for linear resistance load
Harmonics 2nd - 41st free programmable
Current
Test current output 3× (1mA - 120A)
Power of the current output 3×150VA
Resolution Better than 0.01% of full scale value of range
Setting accuracy Better than 0.05% at the final range value
Stability Better than 0.003%/h (integration time 150 s)
Load regulation from 0-max. load < 0.01%
Distortion factor < 0.3% for linear resistance load
Harmonics 2nd - 41st free programmable
Phase angle
Range 0 -- 360°
Resolution 0.01°
Setting accuracy 0.1°
Frequency
Range 45Hz - 65Hz
Resolution 0.01Hz



Stationary Three Phase Meter Test System 0